Electrical
Exposed Wiring at a Water Heater
Status Immediate Safety Concern
Open electrical covers and exposed splices on a water heater create a shock and fire risk at an always-on appliance.
View case fileTHE HOUSE FILES · Electrical
Outdoor GFCI protection that will not trip, shows moisture damage, or otherwise fails the safety device homeowners rely on outdoors.

Exterior receptacles in wet or damp locations need working GFCI protection. A GFCI that will not trip, has no power, or shows heavy corrosion should be repaired or replaced by a qualified electrician—not left in service as if it were protecting people outdoors.
PROMPT EVALUATION
Have a licensed electrician test and replace failed outdoor GFCI devices, repair moisture-damaged covers/boxes, and confirm exterior receptacles are properly protected.
Do not keep using an outdoor receptacle that fails GFCI testing, especially in wet conditions.
GFCI devices open the circuit when they sense a ground-fault imbalance—exactly the shock scenario that happens outdoors with wet conditions and grounded surfaces.
When the device will not trip, or moisture has clearly damaged the assembly, that protection may be unreliable. Exterior covers and gaskets matter too; they keep water out of the box.
A photograph of corrosion documents moisture exposure. Testing confirms whether the GFCI still functions.
In a real inspection, an exterior GFCI on the front porch would not trip when tested and was recommended for replacement. Outdoor receptacles also commonly show moisture staining or corrosion that suggests the protection device should be evaluated or replaced.